Three-Phase Electric Energy Meter Test Equipment with ICT

Three-Phase Electric Energy Meter Test Equipment with ICT
Product Detailed
Related Categories:Testing Equipment
1. Aluminum alloy material 2. Closed I-P link testing 3. Measuring the different constant meters synchronously

Features:

Meter under testing: 3P4W, 3P3W, 1P2WTesting mode: active power, reactive power, cross connection reactive powerWith ICT in each meter position to test three-phase meters with closed links between the current and voltage measuring circuits (I-P links)Neutral current test(optional)Installing RS232, Ethernet communication port in each meter position,to reality the automatic calibrate of electronic meter(optional)  

Specification:

 

YC1893DI-6

YC1893DI-12

YC1893DI-24

Number of meter positions

6

12

24

Accuracy

0.05

Power Source

YCS-103-600

YCS-103-1200

YCS-103-2500

Standard Meter

SZ03A-K6

ICT

6pcs

12pcs

24pcs

QCD

S5 series

Scanning Head

YCG-2 series

Voltage

Test voltage output (Phase-Neutral)

3×(24V – 288V) (or customized )

Power of the voltage output

3×250VA

3×500VA

3×1000VA

Resolution

Better than 0.01% of full scale value of range

Setting accuracy

Better than 0.05% at the final range value

Stability

Better than 0.005%/h (integration time 150 s)

Load regulation from 0-max. load

Better than 0.01%

Distortion factor

Better than 0.3% for linear resistance load

Harmonics

2nd – 21st free programmable

Current

Test current output

3×(1mA – 100A)

Power of the current output

3×350VA

3×750VA

3×1500VA

Resolution

Better than 0.01% of full scale value of range

Setting accuracy

Better than 0.05% at the final range value

Stability

Better than 0.005%/h (integration time 150 s)

Load regulation from 0-max. load

Better than 0.01%

Distortion factor

Better than 0.3% for linear resistance load

Harmonics

2nd – 21st free programmable

Phase angle

Range

0 -- 360°

Resolution

0.01°

Setting accuracy

0.1°

Frequency

Range

45Hz – 65Hz

Resolution

0.01Hz

Error display

Type of error display

Red LED

Resolution of the error displays

8 digits

 

Voltage Supply

3×220/380V±10% or customized

50/60Hz±2Hz

Ambient temperature

-10°C -- +40°C

Relative humidity

35% -- 85%

Three-Phase Electric Energy Meter Test Equipment with ICT